실증 실험을 통한 방화문 두께 변화가 기밀성과 단열 성능에 미치는 영향

원문정보

An Experimental Study on the Effects of Fire Door Thickness on Airtightness and Thermal Insulation Performance

장운성

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

This study experimentally investigated the effects of fire door thickness on airtightness and thermal insulation performance for apartment unit entrance doors. Fire door specimens with thicknesses of 45, 55, 65, and 75 mm were tested for airtightness in accordance with KS F 2292 and for thermal transmittance in accordance with KS F 2278. The airtightness test results showed that all specimens satisfied the Grade 1 requirement. However, no consistent reduction in infiltration rate was observed with increasing door thickness. In contrast, thermal insulation performance exhibited a clear dependence on thickness. The thermal transmittance (U-value) decreased from 1.58 [W/(m²·K)] at 45 mm to 1.23 [W/(m²·K)] at 75 mm. Regression analysis revealed a strong negative correlation between door thickness and thermal transmittance (r = −0.958, p < 0.05). These results indicate that airtightness and thermal insulation performance respond differently to changes in fire door thickness.

목차

Abstract
1. 서론
1.1 연구배경 및 목적
1.2 연구범위 및 방법
2. 이론적 고찰
2.1 방화문의 기능적 특성과 열적 성능 요구
2.2 기밀성과 단열성의 기술적 정의 및 특성
2.3 관련 선행연구 고찰
3. 실험개요
3.1 시험체 구성
3.2 기밀성 시험
3.3 단열성 시험
4. 시험결과 및 분석
4.1 기밀성 시험 결과
4.2 단열성 시험 결과
4.3 시험 분석 결과
5. 결론