원문정보
A Study on Reducing Fire Non-Suppression Probability through the Application of Air Sampling Detectors in Nuclear Power Plants
초록
영어
Purpose: This study aims to calculate the fire detection failure probability using a developed air sampling detector as a method to reduce the NSP (Non-Suppression Probability) for fire CDF(Core Damage Frequency) reduction. Method: As suggested in NUREG-2180, the application methodology for air sampling detectors is presented. The calculation process of Unreliability and Unavailability was used to analyze the results of 400 field installations. Result: The fire detection failure probability of the developed air sampling detector was calculated as 0.0028, confirming a 46% reduction compared to the existing smoke detector failure probability of 0.05. Conclusion: It is judged that this can ultimately contribute to CDF reduction. It is expected that new methods will be proposed through future comprehensive studies considering the severity factor influenced by cabinet fires and cable fires.
한국어
연구목적: 본 연구는 화재 CDF 저감을 위해 NSP(화재진압실패확률)을 저감하기 위한 방법으로 개발된 공기흡입형 감지기를 통해 화재 감지 실패 확률을 계산하고자 한다. 연구방법: NUREG-2180에서 제시 한 바와 같이 공기흡입형 감지기의 대해 적용 방법론을 제시하고 있으며 Unreliability, Unavailability의 계산과정을 통해 400대의 현장 설치 결과를 계산하였다. 연구결과: 개발된 공기흡입형 감지기의 화재 감지 실패확률은 0.0028로 기존 연기감지기 감지 실패확률 0.05의 46% 저감을 할 수 있음을 확인하였 다. 결론: 최종적으로 CDF 저감에 기여할 수 있을 것으로 판단되며 추후 케비닛 화재, 케이블 화재에 영 향을 고려하는 심각도와 복합적인 연구를 통해 새로운 방법이 제시될 것으로 기대된다.
목차
요약
서론
이론적 고찰
화재 CDF(Core Damaged Frequency)
NSP(Non Suppression Probability)
화재 감지 실패확률
Unreliability의 계산
Unavailability의 계산
연구방법
테스트 베드 장소 설치
화재 감지 실패 확률 계산
결과
결론
Acknowledgement
References