원문정보
Development of Sprinkler Head Integrated with Smoke Detector
초록
영어
We developed a smoke detector-integrated sprinkler head that combines smoke detection and automatic fire suppression into a single unit. To overcome the structural limitations of conventional systems requiring separate installation, we designed the two devices as an all-in-one configuration by integrating the smoke detector, control circuit, solenoid valve, heat-sensitive element, and discharge outlet. When smoke is generated, the detector senses it, and the control unit opens the solenoid valve to allow water to flow; rising temperature then activates the heat-sensitive element, rupturing the glass bulb and initiating discharge. A built-in power supply ensures independent operation without external electricity, and a wireless communication module enables real-time transmission of device status to the fire control center. This system can be especially effective in compact or unmanned environments where rapid response and efficient use of space are critical. This design improves spatial efficiency and reduces installation costs, enhancing both economic value and field applicability.
한국어
우리는 연기 감지와 자동 소화 기능을 하나의 장치에 통합한 연기감지기 겸용 스프링클러헤드를 개발하였다. 기존의 연기감지기와 스프링클러헤드가 각각 별도로 설치되어야 했던 구조적 한계를 해결하고, 설치 효율성을 향상시 키기 위해 두 장치를 일체형으로 구성하였다. 각각의 연기감지기, 제어회로, 솔레노이드밸브, 감열체, 방수구 등의 부 품을 하나로 통합하였다. 화재 발생으로 연기 발생 시 연기감지기가 이를 감지하고 제어부가 솔레노이드밸브를 개방 하여 소화수를 유입시키며, 이후 온도 상승에 따라 감열체가 작동하여 유리벌브가 파손되고 방수가 개시되는 작동 원 리를 구현하였다. 또한 이 장치에 자체 전원 공급 장치를 포함시켜 외부 전원 없이도 독립 작동이 가능하도록 하였 고, 제어부에 무선 통신 기능을 탑재하여 연기 감지, 스프링클러헤드 작동 상태, 전원 상태 등의 정보를 실시간으로 방재센터에 전송할 수 있도록 하였다. 이 장치를 통해 설치 공간의 활용도를 높이고, 기존 시스템에 비해 시공이 간 단하여 설치비가 적게 소요되는 경제적 장점을 확보함으로써 현장 적용성과 실용성을 동시에 제시하였다.
목차
Abstract
Ⅰ. 서론
Ⅱ. 이론 고찰
Ⅲ. 구성 및 작동 원리
1. 구성요소
2. 작동 메커니즘
Ⅳ. 시스템의 효율성과 신뢰성 분석
1. 시스템의 효율성
2. 신뢰성 분석
3. 기존 시스템과의 비교 분석
Ⅴ. 결론
References