원문정보
Design of UPS Type Emergency Ventilation System for Agricultural and Livestock Farms
초록
영어
Poultry and pig farms are equipped with ventilation fans as windowless farms, and when commercial power supply is stopped due to short-circuit accidents and power outages, the temperature rise inside the shed causes mass deaths of animals. In this research, the charging part of the UPS type emergency ventilation system is designed to charge a storage battery to operate one ventilation fan for 6 hours continuously and to supply power from the inverter part that converts AC 380V by boosting the DC 540V. In order to solve the problem of temperature generation of the MOSFET in the emergency ventilation system, the transformer output voltage was boosted to 540V and the current distribution circuit was composed of four MOSFETs. It is judged that stable and continuous operation is possible because the MOSFET temperature operates under conditions lower than 60°C by 17°C. The lithium iron phosphate storage battery can be discharged at 30A for 6 hours, and a sequence circuit is designed for stable supply of power in case of an emergency. In addition, power failure detection was performed using the temperature sensor signal value, so that the ventilation system was automatically operated.
한국어
양계 및 양돈농장은 무창 농장으로 환기팬이 설치되어 있으며, 단락사고 및 정전으로 인해 상용전원공급이 중단되면 축사 내부의 온도 상승으로 동물들의 집단폐사의 원인이 되고 있다. 본 연구에서의 UPS형 비상 환기장치 의 충전부는 환기팬 1개를 6시간 연속 가동하기 위한 축전지를 충전시키고, 부스트회로로 DC 540V로 승합하여 AC 380V를 변환하는 인버터부에서 전력공급이 가능하도록 설계되었다. 비상 환기시스템의 MOSFET의 온도발생 문제 를 해결하기 위해서 변압기 출력전압을 540V로 승압 후 MOSFET 4개로 전류분배 회로로 구성하였다. MOSFET 온도는 60℃ 보다 17℃ 낮은 조건에서도 동작함으로써 안정적이고 지속적인 동작이 가능할 것으로 판단된다. 리튬 인산철 축전지는 30A로 6시간 방전 가능하며, 비상상황 발생 시 전력의 안정적인 공급을 위하여 시퀀스회로를 설계 하였다. 또한 온도 센서 신호값을 이용하여 정전 검출을 하여 환기시스템이 자동으로 작동하도록 하였다.
목차
Abstract
Ⅰ. 서론
Ⅱ. UPS 전력변환회로 설계
Ⅲ. 실험 및 결과
Ⅳ. 결론
REFERENCES