A Experimental Study on the Fire Risk of Loaded Equipment due to Floating Neutral
초록
영어
When the neutral conductors ares floated from the three-phase four-wire distribution power system, the three-phase voltage is distributed to the single-phase load device connected to the system in proportion to the impedance. An over-voltage is applied to a single-phase load device with a high internal impedance, and a fire may occur due to deterioration of an internal device of the load devices to which the over-voltage is applied, or dielectric breakdown of a coil or wire insulation coating. Therefore, in this study, the heating characteristics that appear in the process of applying an unbalanced voltage due to the departure of the neutral line and the risk of ignition through electrical signal analysis were confirmed with two types of load devices installed in the three-phase four-wire distribution system.
한국어
3상 4선식 배전계통에서 중성선이 단선되거나 중성선 단자가 이탈되는 경우 3상 전압이 단상부하의 내부 임피던스에 비례하여 직렬로 인가된다. 내부 임피던스가 높은 단상 부하 에는 정격전압보다 높은 과전압이 인가되며, 과전압이 인가된 부하 장치의 내부 소자가 열 화되거나 코일 또는 전선의 절연피복의 절연파괴 등으로 화재의 위험이 높아진다. 따라서 본 연구에서는 3상 4선식 배선계통에 설치된 2종의 부하장치에서 중성선 이탈에 의한 불평 형전압 인가과정에서 나타나는 과열특성과 전기적 신호의 해석을 통하여 발화위험성을 확 인하였다.