가변용량 공조시스템의 난방성능에 대한 실험 연구

원문정보

Experimental Study on Heating Performance of Variable Capacity A/C System

권영철

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

In this study, the heating performance of a variable capacity A/C system was experimentally studied. A psychrometric calorimeter was used to obtain performance data of the A/C system using PWM(pluse width modulation) method and compare it with the compressor discharge temperature correlation equation. Heating capacity, COP, and compressor discharge temperature were obtained by changing indoor and outdoor temperatures, refrigerant amount, and loading duty. The following results were obtained by selecting 5 types of refrigerant amount, 3 types of outdoor temperature (fixed indoor temperature), and 2 types of loading duty. As the outdoor temperature increases, heating capacity and COP increase. Heating capacity was affected by both outdoor temperature and loading duty. However, COP was more influenced by outdoor temperature. The effect of increasing the amount of refrigerant on the performance of the A/C system was not significant. Additionally, the temperature deviation between the existing compressor discharge temperature correlation equation and the heating experiment data was about 5.1℃ at the maximum loading duty.

목차

ABSTRACT
1. 서론
2. 실험방법 및 장치
3. 실험 결과
4. 결론
References

저자정보

  • 권영철 Young-Chul Kwon . Department of Mechanical Engineering, Sunmoon University