가변용량 공조시스템의 냉방성능에 대한 실험 연구

원문정보

Experimental Study on Cooling Performance of Variable Capacity A/C System

권영철

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

In this study, the cooling performance of a variable capacity A/C system was experimentally studied. A psychrometric calorimeter was used to obtain performance data of the A/C system using the pulse width modulation method and compare it with the compressor discharge temperature correlation equation. Cooling capacity, COP, and compressor discharge temperature were obtained by changing indoor and outdoor temperatures, refrigerant amount, and loading duty. The following results were obtained by selecting 5 types of refrigerant amount, 3 types of outdoor temperature (fixed indoor temperature), and 2 types of loading duty. As the outdoor temperature increased, cooling capacity and COP according to outdoor conditions decreased. And the higher the loading duty, the greater the cooling capacity, but the COP was minimal. The change in cooling capacity and COP due to the increase in refrigerant amount was not significant. Additionally, the change in compressor discharge temperature is more influenced by the outside temperature than by the loading duty.

목차

ABSTRACT
1. 서론
2. 실험방법 및 장치
3. 실험 결과
4. 결론