The change in the performance of the range hood according to the pressure change was investigated through a comparative experiment, and the conclusion is as follows. KS C 9304: In 2020, static pressure was applied at 100 Pa according to the fan standard, and the test was conducted by varying the outlet diameter and power consumption. In the case of Motor power 55W, the air volume value was 184.6 when the outlet diameter was 125mm. As a result of the test, if the power consumption is 52.0W, the diameter of the outlet is 125mm, and the power consumption is 60.8W, and the diameter of the outlet is 100mm, it meets 160 or more and less than 200 (constant pressure 100Pa).