earticle

논문검색

수직 행거 내진설계용 스티프너의 단조 압축 실험

원문정보

Monotonic Loading Tests on Seismic Stiffeners for Vertical Hangers

오창수, 공하성

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

In piping systems, trapeze hangers are subjected to vertical and horizontal seismic loads and stiffeners are used. In this study, monotonic compression tests were conducted with the removable stiffeners using three variables: stiffener clamp fixing position, section length, and installation direction. The maximum load reinforced with stiffeners could withstand a compressive load of 11kN by applying a safety factor of 10%. It could be estimated that the fixing clamp spacing or the length of shape and load had a proportional relationship. And the stiffener must be fixed in the direction of the strong axis on hinge parts. Also the stiffener buckiling load design proposes to use a method of calculate the flexural buckling compressive strength of and unreinforced full threaded bolt.

목차

Abstract
1. 서론
2. 실험 계획
2.1 실험 방법
2.2 실험체 계획
2.3 실험 재료
3. 실험 결과
3.1 좌굴 양상
3.2 최대 하중
3.3 스티프너의 압축하중 평가
4. 결론
5. References

저자정보

  • 오창수 Chang-Soo Oh. 우석대학교 일반대학원 소방·안전공학과 박사과정
  • 공하성 Ha-Sung Kong. 우석대학교 일반대학원 소방방재학과 교수

참고문헌

자료제공 : 네이버학술정보

    함께 이용한 논문

      ※ 기관로그인 시 무료 이용이 가능합니다.

      • 4,000원

      0개의 논문이 장바구니에 담겼습니다.