The reduction of the smoke exhaust performance of the natural smoke ventilator due to the influence of the external wind speed causes the problem of not being able to appropriately exhaust the heat and smoke generated by the fire compartment into the outflow air, which has a huge impact on the evacuation of the occupants, and at the same time can be a major problems to remaining life safety and fire suppression of the fire brigade. In this study, the type of projected window natural smoke ventilators opening to exterior which was selected from the preliminary smoke performance evaluation study and then the fire simulation was performed to quantitatively evaluate the smoke exhaust performance of the n atural smoke v entilator by the s iz e of the outside w ind speed. A s a result of the analysis, a s the wind speed increased, the smoke exhaust performance of the natural smoke ventilator was further reduced, and the amount of flue smoke due to the inlet flow was reduced, and it was predicted to negatively affect the main evacuation factors such as smoke layer height and fire room temperature.
한국어
외기풍속의 영향으로 인한 배연창의 배연성능 감소는 화재실에서 발생하는 열 및 연기를 외기로 충분하게 배출시키지 못하는 문제를 야기함으로써 재실자의 피난에 막대한 영향을 주는 것과 동시에 소방대의 인명구조 및 화재진압에 큰 장 애가 될 수 있다. 본 연구에서는 기 수행되었던 배연창 유형별 배연성능 평가 연구에서 가장 우수한 배연성능을 갖춘 외 기 개방형 배연창을 분석대상으로 선정하고 이에 대한 화재시뮬레이션을 수행함으로써 외기풍속 크기별 배연창의 배연 성능을 정량적으로 평가하였다. 분석결과 외기풍속이 증가할수록 배연창의 배연성능을 더욱 감소되어 유입풍속에 따른 배연량 감소되었으며, 연기층 높이, 화재실 온도 등의 주요 피난인자에 부정적영향을 미치는 것으로 예측되었다.
목차
요약문
1. 서론
1. 연구배경
2. 연구목적
2. 본론
1. 화재모델링
2. 분석결과
3. 배연성능 여유도(Safety margin)
III. 결론
References