earticle

논문검색

조직 분석(ASTM E1382)에 의한 용융흔 정량적 판별 연구

원문정보

Quantitative Analysis of Electrical Molten Marks Applying ASTM E1382

은희림, 김용범, 정승태, 홍춘호

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

The molten marks of electrical wiring found at the fire site can be helpful in inferring the cause of the fire and the ignition point, and it is a very important piece of evidence. However, in the fire department, there are few cases of quantitative analysis and study on the texture of molten marks. In this study, based on the ASTM E1382 standard, using an analysis program called iSolution DT, the image taken with an electron microscope is analyzed and quantitatively determined. In a energized state, the electric wiring was short-circuited at 25°C and 600°C to form molten marks. The primary melt scar shorted at 25°C showed a small columnar structure major axis ratio (GAR), and the secondary melt scar shorted at 600°C showed a large major axis ratio (GAR). As a result, it will be very helpful in quantitatively classifying primary and secondary melt traces using isolution DT.

목차

Abstract
1. 서론
2. 실험 개요 및 실험 방법
2.1 실험 개요
2.2 실험 방법
2.3 실험 결과 및 분석
3. 실험 결과 및 고찰
3.1 구리의 단면 조직 분석 이론
3.2 전선 용융흔(단락흔)의 단면 조직 분석
4. 연구 결과 및 고찰
5. 결론
참고문헌

저자정보

  • 은희림 Hee-Rim Eun. 전북소방본부 정읍소방서
  • 김용범 Young-Beom Kim. 전북소방본부 정읍소방서
  • 정승태 Seung-Tae Jeong. 전북소방본부 정읍소방서
  • 홍춘호 Chun-ho Hong. 전북소방본부 정읍소방서

참고문헌

자료제공 : 네이버학술정보

    함께 이용한 논문

      ※ 기관로그인 시 무료 이용이 가능합니다.

      • 4,800원

      0개의 논문이 장바구니에 담겼습니다.