초록

영어

In the present study, to investigate the cooling characteristics of the multi-heat pump with 3 indoor units, 7 indoor unit combinations and 3 setting temperatures are selected to study the cooling characteristics during steady-state operation. The cooling capacity, power consumption, COP, compressor high and low pressure of the heat pump are tested under the cooling standard temperature conditions using an air enthalpy multi-calorimeter. The experimental results show that, except for an operation with an indoor unit capacity of 30% or less, the cooling capacity, power consumption, and compressor operation frequency increase as the capacity of the indoor unit increases and the setting temperature of the indoor unit decreases. COP increases or decreases according to the compressor frequency, and is the best at 50-80% capacity of the indoor unit. As the compressor frequency increases, the compressor outlet pressure increases by about 30%.

목차

ABTRACT
1. 서론
2. 실험장치 및 실험방법
2.1 실험장치
2.2 실험방법
3. 실험결과 및 분석
4. 결론
References

저자정보

  • 권영철 Young-Chul Kwon. Member, Department of Mechanical Engineehng, Sunmoon University (Research Institute for Industrial Technology)