Energy Storage System (ESS) is a facility that can store electricity and supply power when needed, and is a very necessary element for new and renewable energy generation. Thermal runaway fires can occur due to various causes in ESS. These fires can cause different damage depending on the building structure and other building disaster prevention facilities. Therefore, it is necessary to evaluate the fire risk by deriving the frequency of occurrence of the cause of fire in the ESS and checking the severity factor that determines the damage scale. In this study, fire risk assessment of ESS was performed using risk matrix method. The risk assessment was conducted based on data collected based on fire cases and field investigations. Through risk assessment, it was confirmed that the main causes of ESS fires were EMS/BMS errors and battery abnormalities. In addition, as the structure of the ESS building is fire-resistant, the fire compartment is set, and the separation distance between battery facilities is larger, the damage caused by a fire is smaller.
목차
Introduction
Study Method
Scope
Risk Assessment Method
ESS Fire Case
Fire Status
Fire Scene Investigation Case
Jeonbuk ○○ Sunlight Case
Sejong ○○ Paper Case
Chungbuk ○○ Cement Case
Ulsan ○○ Gas Case
Seoul ○○ Building Case
Fire Risk Assessment
Determine the Risk Criteria
Assess the Risk
Prioritize the Risks
Fire Risk Assessment
Acknowledgement
References