히트펌프식 건조기의 성능특성에 대한 실험연구

원문정보

Experimental Study on Performance Characteristics of Heat Pump Dryer

권영철

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

In order to study the drying performance of the dryer, the performance characteristics of the heat pump dryer applied a PF heat exchanger is applied were experimentally investigated. The capacity, COP, drain and SMER of the dryer were measured by the refrigerant charge and EEV opening. Heat pump dryers are refrigerant-air systems. For the dryer performance test, an air enthalpy calorimeter was used. From the experimental results, the heat exchanger performances according to the change in the refrigerant charge and EEV opening were the maximum at 0.5kg refrigerant and 30% EEV opening, respectively. In addition, SMER suggested a satisfactory level of drying performance. This shows that the refrigeration cycle of the dryer must be operated at an appropriate refrigerant amount and EEV opening degree to secure optimal drying performance. On the other hand, the time to reach the target setting temperature of the dryer was increased by about 2.5 times depending on with/without the sample.

목차

ABSTRACT
1. 서론
2. 실험장치 및 방법
2.1 실험장치
2.2 실험방법
3. 실험결과
3.1 냉매 충진량 변화에 따른 성능특성
3.2 EEV개도 변화에 따른 성능특성
3.3 건조성능
4. 결론
References

저자정보

  • 권영철 Young-Chul Kwon. Member, Department of Mechanical Engineering, Sunmoon University