주거공간 에어로 시스템 배치에 관한 화재시뮬레이션 연구

원문정보

A Study on Fire Dynamics Simulation on the Arrangement of Aero System in the Residential

최두찬, 고민혁, 이두희, 박계원, 최정민, 이용권, 김길남, 선경수

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

Purpose: The called Aero System is important to find the well detected place in the livingroom or bedroom so, it needs to the confirmation through the Fire Dynamics Simulation Method: A fire simulation of a residential space of 59 m² was performed, and in order to find the point where the fire environment was exposed quickly, measuring points were installed at 0.6 m and 1.5 m in height for each bedroom and living room, and the point where the fire was quickly detected was confirmed. Result: It was confirmed that the temperature and carbon monoxide sensor set at a point of 1.5 m was quickly detected at the reference value. Conclusion: The Fire detection would be relatively quick if the product in which the fire extinguishing module and the AQI module were separated was installed on the wall.

한국어

연구목적: ‘에어로 시스템’이란 제품을 개발하였으며, 화재 특성상 신속한 감지가 무엇보다 중요함으 로 개발하고 있는 제품을 주거 공간 어느 지점에 배치를 하였을 때 신속하게 감지를 할 수 있는지 화재 시뮬레이션을 통해 확인하고자 하였다. 연구방법: 18평형의 주거 공간에서 화재시뮬레이션을 수행하 였으며, 화재 환경이 빨리 노출되는 지점을 찾고자 침실, 거실 별로 측정점을 높이 0.6m, 1.5m 지점으로 설치하여 빨리 감지 되는 지점을 확인하였다. 연구결과: 대부분 1.5m 지점으로 설정한 온도 및 일산화 탄소 센서가 기준 치에 빨리 감지 되는 지점을 확인하였다. 결론: 소화모듈과 AQI모듈이 분리된 제품을 벽에 부착형으로 설치할 경우 화재 감지가 상대적으로 빠른 것으로 확인되었다.

목차

ABSTRACT
요약
서론
조기화재 감지 및 화재 진압 시스템
구성 요소
디자인 선정
제품 배치에 관한 연구
연구 방법
화재시뮬레이션 입력조건
결과
결론
Acknowledgement
References

저자정보

  • 최두찬 Doo Chan Choi. Chef Exeuctive Officer, KFUBIS, Seoul, Republic of Korea
  • 고민혁 Min Hyeok Ko. Senior Researcher, KFUBIS, Seoul, Republic of Korea
  • 이두희 Doo Hee Lee. Researcher, KFUBIS, Seoul, Republic of Korea
  • 박계원 Kye Won Park. Principal Researcher, Fire Insurers Laboratories of Korea, Yeoju, Republic of Korea
  • 최정민 Jeong Min Choi. Senior Researcher, Fire Insurers Laboratories of Korea, Yeoju, Republic of Korea
  • 이용권 Yong Kwon Lee. Vice President, Samwoo Instrument, INC, Seoul, Republic of Korea
  • 김길남 Gil Nam Kim. Research Engineer, Samwoo Instrument, INC, Seoul, Republic of Korea
  • 선경수 Kyoung Soo Sun. Team Manger, INTENXIV, Seoul, Republic of Korea

참고문헌

자료제공 : 네이버학술정보
  • 1Choi, J.-M., Park, K.-W., Jeong, J.-G., Lee, Y.-K., Kim, G.-N., Choi, D.-C., Ko, M.-H. (2021). “Experimental study on the availability of fire detection using gas sensors for air quality measurement.“ Fire Science and Engineering Vol. 35, No.1, pp. 41-47.
  • 2Choi, S.G., Young, J.S., Park, S.M., Nam, Y.J., Kim, S.K. (2020). “Basic research on potential application of fire detection by measuring fire detection tendency of indoor air quality measurement factors.” Fire Science and Engineering, Vol. 34, No. 1, pp. 37-46 .
  • 3Kim, D.H., Jo, B.W. (2021). “A study on the development of a fire site risk prediction model based on initial information using big data analysis.” Journal of The Korean Society of Disaster Information, Vol. 17, No. 2, pp. 245-253.
  • 4Lee, H.J., Ryu, J.R., Chung, M.H., Kim, M.G., Sang, H. (2019). “Optimal control method of indoor air quality in apartment using integrated sensor for indoor environment.” Proceedings of the Society of Air-Conditioning and Refrigerating Engineers of Korea, pp. 108-110.
  • 5Park, H.-W. (2013). Experimental and Numerical Studies on Device Characteristics of Smoke and Heat Detectors. Ph.D. thesis, Daejeon University, Korea.
  • 6Ryu, H.C. (2014). “Analysis on activation characteristic of heat detectors in a compartment fire.” Journal of The Korean Society of Disaster Information, Vol. 10, No. 4, pp. 598-608.
  • 7Ryu, H.C. (2015). Analysis of Response Time of Heat Detectors by Installation Location and Fire Source in a Compartment Fire. Ph.D. thesis, Chungbuk National University, Korea.
  • 8Son, G-S., So, S.H. (2021). “A study on fire alarm test of IoT multi-fire detector combined Smoke/CO and Smoke/Temperature sensors.” Journal of The Korean Society of Disaster Information, Vol. 17, No. 2, pp. 236-244.
  • 9Torkmahalleh, M.A., Goldasteh, I., Zhao, Y., Udochu, N.M., Rossner, A., Hopke, P.K., Ferro, A.R. (2012). “PM2.5and ultrafine particles emitted during heating of commercial cooking oils.” Indoor Air, Vol. 22, No. 6, pp. 483-491.

※ 기관로그인 시 무료 이용이 가능합니다.

  • 4,000원

0개의 논문이 장바구니에 담겼습니다.