영어
This study analyzed the changes in carbon monoxide, carbon dioxide, oxygen and visual distance by presence of sprinkler heads and their types in the event of a fire in an indoor gymnasium. Based on carbon monoxide and visual distance that affects human bodies enormously, first, if there is no sprinkler head, carbon monoxide will reach 0.4% within five seconds and visual distance rapidly shrank within five seconds. Seconds, in the event of standard sprinkler heads, carbon monoxide gradually increased from 30 seconds onwards and visual distance rapidly shrank after five seconds. Second, Third, if there are special sprinkler heads, carbon monoxide fluctuated after opening the head and visual distance became 5m or below from 15 seconds. Finally, in the event of early response sprinkler heads, carbon monoxide fluctuated up and down at 3 seconds due to falling water drops. Visual distance shrank up to 5m or below at 6 seconds. In the future, time for operation of each sprinkler head shall be analyzed.
목차
1. Introduction
2. Fire Simulation
2.1 Structure of Fire Simulation
2.2 Fire Scenario
2.2 Fire Simulation Program Input
3. Results and Discussions
3.1 Changes of carbon monoxide in the Fire-affected Area
3.2 Changes of carbon dioxide in the Fire-affected Area
3.3 Changes of oxygen in the Fire-affected Area
3.4 Change of Visibility Range in the Fire-affected Area
4. Conclusion
References