DC Superconducting fault current limiter characteristic test with a DC circuit breaker

초록

영어

We have studied the breaking system that combines a resistive superconducting fault current limiter (SFCL) and a DC circuit breaker for DC fault current. To verify the design of the 15 kV DC SFCL, which was driven from the previous work, a 500 V DC system was built and a scale-down SFCL were manufactured. The manufactured SFCL module was designed as a bifilar coil which is a structure that minimizes inductive reactance. The manufactured SFCL module has been experiment to verify characteristics of the current-limiting performance in the DC 500 V system. Also, the manufactured FCL module was combined with the DC circuit breaker to be experimented to analyze the breaking performance. As a result of the experiment, when SFCL was combined to the DC circuit breaker, the energy dissipation received by the DC circuit breaker was reduced by up to 84% compared to when the DC circuit breaker operates alone. We are preparing methods and experiments for the optimal method for much higher performance as a future work.

목차

Abstract
1. 서론
2. 500 V 한류 모듈 제작
3. 500 V 저항형 한류 모듈 특성 시험
3.1. 모의 단락시험 시스템 제작
3.2. 500 V 저항형 한류 모듈 특성
4. 차단기 연계 시험
5. 결론
ACKNOWLEDGMENT
REFERENCES

저자정보

  • Jooyeong So Korea Polytechnic University, Gyeonggi-do, Korea
  • Kyeongdal Choi Korea Polytechnic University, Gyeonggi-do, Korea
  • Ji-kwang Lee Woosuk University, Jeollabuk-do, Korea
  • Woo-Seok Kim Korea Polytechnic University, Gyeonggi-do, Korea

참고문헌

자료제공 : 네이버학술정보

    함께 이용한 논문

      ※ 기관로그인 시 무료 이용이 가능합니다.
      ※ 학술발표대회집, 워크숍 자료집 중 4페이지 이내 논문은 '요약'만 제공되는 경우가 있으니, 구매 전에 간행물명, 페이지 수 확인 부탁 드립니다.

      • 4,000원

      0개의 논문이 장바구니에 담겼습니다.