원문정보
Causes of spontaneous ignition of Coal and fire in transfer facility
초록
영어
In order to review the fires of domestic coal transfer facilities and take countermeasures to prevent recurrence, it is difficult to fundamentally prevent spontaneous ignition of coal, especially spontaneous ignition of sub-bituminous coal containing volatile contents. The spontaneous ignition of the generated suspended dust acts as an ignition source, causing a small dust explosion in the TT or BB and the rapid expansion of the combustion due to the secondary large-scale dust explosion caused by the floating of the secondary dust caused by the impact of the small dust explosion. It turned out that it developed into fire. To prevent this, it is necessary to minimize the spontaneous ignition conditions, design the transfer facility considering the flame combustion generated from sub-bituminous coal, which is a high volatile component, and control the dust explosion conditions. As it is impossible to suppress, O2 control equipment is proposed as an alternative in the dust generating locations TT and BB.
한국어
국내에서 발생한 석탄이송설비의 화재를 재검토 하고 재발방지대책을 강구하고자 연구한 결과 석탄의 자연발화 특히 휘발성분이 다량 함유된 아역청탄의 자연발화를 근본적으로 예방하기 어려우며, 이의 이송과정에서 발생하는 화재는 발생된 부유분진 에 자연발화된 불씨가 점화원으로 작용하여 TT나 BB에서 소규모 분진폭발이 일어나 고 소규모 분진폭발에 의한 충격으로 2차적으로 발생된 분진의 부유에 의하여 2차 대 규모 분진폭발로 연소가 급격히 확대되어 화재로 발전하는 것을 알 수 있었다. 이의 예방을 위해서는 자연발화조건의 최소화 대책, 고함유 휘발성분인 아역청탄 연소에서 발생하는 화염연소를 고려한 이송설비 설계, 분진폭발조건 제어가 필요하며, 아역청탄 자체의 자연발화와 설비상 분진발생의 억제가 불가능한 바 분진발생위치인 TT 및 BB 에서 O2제어설비를 대안으로 제시하고자 한다.
목차
Abstract
1. 서론
1.1 석탄의 자연발화
1.2 석탄의 분류와 자연발화
1.3 석탄의 연소
1.4 가연성혼합기와 가연성혼합분진의 점화원
1.5 석탄 분진의 폭발
2. 사례의 분석
2.1 ○○화력발전소 화재
2.2 한국○○발전 컨베이어 TT-02 화재
2.3 한국○○발전 TT-08 화재
2.4 한국○○발전 CV-13 갤러리화재
2.5 한국○○발전 BB 화재
2.6 저탄장에서의 발화
3. 결론
참고문헌