원문정보
초록
영어
Circulating cooling systems consume a lot of water, and most of the water from river, which contains a large amount of Ca2+, Mg2+, et al, and has the characteristics of high hardness and large turbidity. The water can form scale on the surface of the heat exchanger and the pipes, which would reduce the heat transfer efficiency and affect the heat exchanger’s length of service. In this study, the Superconducting High Gradient Magnetic Separation (S-HGMS) technology was used in river water treatment and the effects of agent A, agent B, and S-HGMS on the removal of hardness and turbidity were discussed. The results showed that the hardness removal rate reached 71.3% and the turbidity was decreased to 0.5 NTU.
목차
1. INTRODUCTION
2. MATERIALS AND METHODS
2.1. Materials
2.2. Analysis of scale
2.3. Experimental system
3. RESULTS AND DISSCUSSION
3.1. Effect of agent A on hardness
3.2. Effect of agent B on turbidity
3.3. Effect of S-HGMS on scale
3.4. Effect of S-HGMS on turbidity
3.5. Effect of S-HGMS and possible mechanism
4. CONCLUSIONS
ACKNOWLEDGEMENTS
REFERENCES