원문정보
Design of seismic isolation system for earthquake resistant electrical cabinet
초록
영어
As the social interest in seismic design of telecommunication facilities increased in the early 2000s, studies on the development of seismic electrical cabinet in ordinary buildings began to be conducted. In Korea, various methods have been suggested to improve the seismic performance of electrical cabinet for ordinary building, but only a few of them are actually used. In this study, seismic isolation device was developed, based on the results of the nonlinear time history analysis, to increase the seismic performance of the electrical cabinet, and the seismic performance was verified by shaking table tests. The results of the analysis and tests are as follows; (1) Proposed simplified model showed the possibility of being usefully used to grasp the dynamic characteristics of the electrical cabinet. (2) As a result of shaking table tests, the maximum bottom shear force was reduced by 55% and operated normally to satisfy the demanded performance of the electrical cabinet. (3) A series of processes performed in this study, seismic isolator can be useful in the development of seismic isolators for electrical cabinet in the future.
목차
1. 서론
2. 수배전반의 지진저항 특성
2.1 수배전반의 횡거동특성과 파괴유형
2.2 내진형 수배전반의 유형
2.3 수배전반 관련 기준
3. 면진형 수배전반의 성능평가
3.1 모델 수배전반의 개요
3.2 유한요소해석모델 방법
3.3 수배전반의 횡성능 도출
3.4 단순해석모델 해석
3.5 지진격리시스템 설계
4. 고찰
4.1 진동대 실험
4.2 해석결과와 비교
5. 결론
REFERENCES