Experiments were conducted on the operating characteristics and performance of various types of working fluid, filling amount and heat flow rate of a loop thermosyphon for cooling ESS battery container. As results of performance test on various working fluids, HFE-7100 and R-134a as a working fluids showed unstable operating and low performance due to vapor pressure drop, and performance was improved by increasing the number of vapor lines for reducing a pressure drop. In this study, n-pentane was more stable and showed better thermal performance among various working fluids.
목차
ABSTRACT
1. 서론
2. 실험장치와 실험방법
3. 결과 및 고찰
3.1 루프 열사이폰의 온도진동
3.2 증기 유동 온도차 및 압력강하
3.3 작동유체의 종류에 따른 열교환기의 성능
4. 결론
후기
References
1. 서론
2. 실험장치와 실험방법
3. 결과 및 고찰
3.1 루프 열사이폰의 온도진동
3.2 증기 유동 온도차 및 압력강하
3.3 작동유체의 종류에 따른 열교환기의 성능
4. 결론