The Development of Harmonic Passive Filter Controller Based on Power Factor Correction
초록
영어
Accidents of electric equipment and economical loss by harmonics show a rising tendency. A passive filter is economic and efficient in suppressing harmonics. But many engineers and designers are reluctant to install a passive filter to defect harmonics at their power system because of problems such as harmonic amplification and the probability of generating series or parallel resonance with the power system. This work have developed harmonic passive filter controller based on power factor correction that passive filters. The volated and current measurement accuracy of the developed system is tested by using electrical power standard devices FLUKE 61000A. The test results showed that accuracy of the developed system is less than 0.5 %
한국어
고조파에 의한 전기설비 사고와 경제적 손실은 증가하고 있다. 고조파 수동 필터는 고조파를 억제하는데 효과적이고 경제적이지만, 많은 현장 엔지니어들은 고조파 증폭과 병렬 공진 발생 등의 문제점으로 인해 계통에 수동 고조파 필터를 설치하는 것을 꺼려한다. 본 논문에서는 이러한 문제점을 해결하기 위해 역률 보상을 기반으로 하는 고 조파 수동필터 제어기를 개발하였다. 개발된 시스템의 전압 및 전류 측정 정확도는 표준 전력 발생장비인 FLUKE 61000A를 이용하여 시험하였으며, 측정 정확도는 0.5% 이하로 나타났다.