미생물 안전을 위한 병원건물의 환기설계에 따른 공기 감염균 확산에 관한 시뮬레이션 연구

원문정보

A Study on simulation analysis of the microbe transport of air-born virus in hospital for microbiological safety

최상곤

피인용수 : 0(자료제공 : 네이버학술정보)

초록

영어

Recently there is a growing interest in the airborne spread of virus. In particular, there is growing interest in secondary infection through the air in the hospital. The distribution of air-born virus depends on ventilation system installed in a hospital. In this study, simulations were carried out to predict the move of air-born virus by ventilation system at hospital. Simulation results showed that pressure distribution was –372.05Pa ∼ -3.45 Pa at 1st floor incase of only used mechanical exhaust at bathroom, shower stall , storage, kitchen etc.. if ventilation switch from used mechanical exhaust to mechanical exhaust & mechanical supply. Simulation results showed that pressure distribution was -336.44Pa at stair hall < -0.2Pa at bathroom < mean 1.19Pa at other room. So simulation results showed that using all of the mechanical supply and mechanical exhaust was more effective then the mechanical exhaust for maintain the pressure distribution in hospital. It was also showed that when using the mechanical supply and mechanical exhaust more effectively prevention of air born virus diffusion.