원문정보
초록
영어
Renewable sources integration is gaining importance in electrical utilities all over the world. The liberization of power sector in competitive regime, the share of renewable energy sources is increasing and it is essential to carry out the impact of clean energy on the system performance In this paper, analysis has been carried out with the PV-based distribution generation in the power system network. A Mixed Integer Nonlinear Programming (MINLP) approach has been utilized for determining optimal location and number of distributed generators considering minimization of fuel cost of conventional and solar PV power. The pattern of nodal real and reactive power prices have been obtained with and without PV integration. The results are also obtained for, loss reduction, fuel cost saving and voltage profile. The impact of different load models as PQ load and Zip load model has been studied. The proposed MINLP based optimization approach has been applied for IEEE24 bus reliability test system.
목차
1. Introduction
2. PV-based DG Power and Cost Function
3. General OPF Formulation
4. Zip Load Model
5. Results and Discussion
6. Conclusions
References