원문정보
P 형수신기 사용자회로의 전기전자구성부품에 대한 고장모드영향분석
초록
영어
This study is aimed to reduce failure rates and failure modes through the arrangement of the list corresponding to the component of the electrical and electronic in the user circuit of a P-type receiver. This paper analyzes a user circuit of monitoring and alarm systems in buildings. In the user circuit, the heaviest failure modes are shown in cables. The results of a risk priority number (RPN) analysis shows that a total of 6 failure modes is shown in the parts of contact/intermittent (112) and arcing/sparking (121) of the cables. Moreover, a mechanical failure (301) and an intermittent/degraded operation (302) of On/Off switch, high contact resistance (401) of a capacitor, and a drift (501) of IC are the other modes of the failure. Consequently, we find that the part of frequent breakdown is the cable and verify that the defect of cable connectors causes lots of failures of user circuits such as contact/intermittent. We expect that these findings will contribute to increase the quality of firefighting supplies and their life-spans.
한국어
본 연구에서는 국내에서 중소형 건축물에 가장 많이 사용되고 있는 5회로 P형수신기를 타깃으로 선정하였고, 5회로 P형수신기의 사용자회로와 메인회로 중에서 사용자회로를 중심으로 전기전자부 품에 대한 위험우선순위지수와 중요도를 도출하였다. 구성부품으로 분석하면 Cable에서 2개 모드, Switch 2개 모드, Capacitor 1 개 모드, IC 1 개 모드로 4 개의 구성부품에서 차지하였다. 고장모드는 Cable 의 poor contact/intermittent(112)와 arcing/sparking(121), Switch의 mechanical failure(301)과 inter-mittent/degraded operation (302), Capacitor의 high contact resistance(401) 및 IC 의 drift(501)이었다. 중요 도에서 가장 높게 나타난 고장모드는 Cable 의 Poor contact/intermittent(112)와 Arcing/sparking(121), Diode 의 Shorted(201)였다. P 형수신기의 경우는 Cable 의 연결하는 커넥터부분의 접속불량이 가장 문 제였으며, 이런 접속부의 접속불량은 아크와 스파크를 동반하고 있어 주위가연물이 존재하면 화재 뿐만 아니라 고장을 일으킬 수 있는 조건으로도 작용하였다. Cable 과 Switch 의 관리 및 내구성이 높은 부품의 변경으로 내구연한을 높일 수 있다.. 본 연구는 인적재난위기의화재와 생활안전위기의 생활용품안전에 활용가능하다.
목차
Ⅰ. 서론
Ⅱ. 이론적 고찰
1. FMEA 기법
2. 위험우선순위지수
3. 중요도 등급기준
Ⅲ. 결과 및 고찰
1. 실태조사에 의한 분석
2. P 형수신기의 주요부품 및 고장률
3. 고장모드영향분석
Ⅳ. 결론
References
국문초록