원문정보
On the study of the development of a program for calculating the heat decay produced by possible iodines captured on the carbon adsorber
초록
영어
An air cleaning unit(ACU) in a nuclear power plant plays a role on cooling the safety-related components whose function is involved in the reactor shutdown, and maintains the suitable temperature and humidity for work in the rooms where an operator is working on. To guarantee the performance of the unit the design of ACU should be subject to credible codes and standards, such as ASME, ANSI and ASHRAE, etc. On top of them, the desorption of the carbon adsorber is addressed in ASME N509 which causes the adsorber no longer to capture the iodine isotopes produced by the severe accident. In this study, the equations of the heat source were derived from the radioactive decay heat of each iodine isotopes. From the resultant equation, the maximum temperature below 300oF for the desorption was calculated under a proposed condition and analysed with the reference results.
목차
1. 서론
2. 방사성 요오드 붕괴열 계산 식
2.1 절 붕괴열 계산 식
3. 개발 프로그램의 검증 및 응용
3.1 절 개발 프로그램의 검증
4. 결론
후기
References