원문정보
Operating Characteristics of Heat Pump using Shell & Coil Heat Exchanger
초록
영어
The heating & cooling performance of vapor compression heat pump using seawater heat source has been investigated experimentally for fish farm heat supply system. The principal parts of the heat pump systems are compressor, condenser, expansion devices and evaporator. The evaporator and condenser are both heat transfer devices. We used double pipe H/E(CASE-1) and shell&coil H/E(CASE-2) as evaporator, condenser of heat pumps. The experimental results were higher Uvalue 25% of double pipe heat exchanger compared to shell & coil H/E. The COPc is 4.74 and the COPH is 6.18 of the heat pump with shell & coil H/E.
목차
1. 서론
2. 실험장치 및 방법
2.1 실험장치
2.2 실험방법
2.3 열교환기 특성
3. 결과 및 검토
3.1 냉각운전 성능
3.2 가열운전 성능
4. 결론
References