초록

영어

Comparative investigations of the conventional analog and optical communication analog fire detector signal attenuations with various numbers of fire detectors were performed in this research. The conventional fire detector signals with 1, 2, 16 and 32 fire detectors were 4.5, 4.0, 2.2 and 0.8 V, respectively. The fire detector signals were drastically decreased with the increase of the number of fire detectors. However, the optical communication fire detector signals were not changed with increasing the number of fire detectors. Therefore, optical communication fire detector system is a promising fire detection system for eliminating the false alarms.

목차

Abstract
 1. Introduction
 2. Experiment
  2.1 Equipment Design and Fabrication
  2.2 Experiment Setup
  2.3 Experimental Method
 3. Results and Discussion
  3.1 The Signal Waveform with Various Communication Loads
  3.2 Test Results
 4. Conclusion
 References

저자정보

  • Ha-Sung Kong Department of Fire Safety, Kyungil University, 50 Gamasilgil Haynagup Gyeongsan Gyeongbuk 712-701, South Korea
  • Jong-Seog Yang Hyundai Infra Core, Inc., 52, Chungmin-ro, Songpa-gu, Seoul, 138-961 South Korea (B-dong, 904-ho, Garden 5WK, Munjung-Dong)
  • Kwang-Sun Kang Department of New and Renewable Energy, Kyungil University, 50 Gamasilgil Haynagup Gyeongsan Gyeongbuk 712-701, South Korea