원문정보
A Feasibility Study on Auto-Jar System for Coagulant-dosing Optimization in Total Phosphorous Treatment
초록
영어
A-MCOS (Advanced Molit Coagulant-dosing Optimization System) equipped with an Auto-Jar was devised for a realtime control of total phosphorus (TP) in secondary effluent, then tested for field applicability starting from May 7 till May 23 in 2014 at J-STP where MCOS was operated in our previous study. The mean coagulant reduction rate by the A-MCOS was 20.5%, compared with a control where coagulant was applied at a constant rate. Total cost for A-MCOS or control operation was estimated by summing up coagulant cost and sludge treatment cost. Thereby, the cost increase by A-MCOS would be 5.0 won/m3, corresponding to one-third of that by MCOS, which would result in 18% of cost reduction compared with a control operation. These results indicate that A-MCOS can be an alternative for TP treatment, with an improved cost efficiency over MCOS.
한국어
2차 침전지 유출수 총인 농도의 실시간 제어를 위하여 Auto-Jar가 장착된 응집제 주입량 최적제어 시스템(Advanced Molit Coagulant-dosing Optimization System, A-MCOS)을 개발하여, 선행 연구의 MCOS가 운전되었던 J-STP에서 2014년 5월 7일부터 23일까지 현장적용 가능성을 검토하였다. Pilot plant 운전 결과, A-MCOS에 의한 응집제 절감율은 정율주입의 대조군과 비교시 평균 20.5%를 나타내었다. 응집제 사용 비용과 응집제 사용에 따른 슬러지발생 처리비용을 합산하여 경제성을 분석하였다. 그 결과 A-MCOS 실험군의 처리비용 증가액은 5.0 won/m3으로 선행연구의 MCOS 운전체계로 발생된 처리비용 증가액의 1/3 수준이었으며, 대조군 대비 18.0%의 비용절감 효과를 나타내었다. 이는 AMCOS가 선행연구의 MCOS보다 향상된 비용효율성을 지니며, TP처리를 위한 현장적용 가능한 대안이 될 수 있음을 시사해주었다.
목차
요약문
I. 서론
II. 재료 및 방법
1. Jar-test
2. A-MCOS의 구성
3. Pilot-plant
III. 결과 및 고찰
1. 처리대상수의 특성 및 Jar-test 결과
2. A-MCOS의 현장적용
3. 경제성 분석
IV. 결론
사사
References