원문정보
초록
영어
This paper makes an assessment of the typical main steam temperature system in thermal power plant. Due to main steam temperature system is a cascade control system. So, it should be assessed with the performance assessment method of cascade control systems. So firstly, this paper deduces the theoretical process of performance assessment of cascade control system based on minimum variance. Then with this method assesses the performance of four typical loads in thermal power plants when using active disturbance rejection-proportion (ADRC-P) cascade control and smith active disturbance rejection-proportion (SADRC-P) cascade control respectively. Finally, makes comparison of the results. Results show that, when using the same control strategy, different loads has different performance. Load with lager inertia has better performance; When using different control strategies, performance under SADRC-P control is better than that under ADRC-P control.
목차
1. Introduction
2. Main Steam Temperature Control System
3. Performance Assessment of Cascade Control System
4. Simulation Results
4.1. Performance Assessment of Different Loads
4.2. Performance Comparison of Different Control Strategies
4.3 Performance Comparison when Smith ADRC in Model Mismatch
5. Conclusion
Acknowledgements
References