Analysis and Experimental Study on Fire Resistance of Load-bearing Walls Made up of Light-gauge Steel
초록
영어
Steel framed house made up of light gauge steels regarded as an alternative to meet the fast construction and high quality for the detached house, warehouse, and etc since the late of 1990's. The steel stud and steel joist applied as primary member and the finishing materials such as gypsum board, plywood would be attached on the frame and to satisfy the insulation and acoustic performance mineral wool would be applied into space between the finishing materials. One hour fire resistance is essential when the steel framed house is utilized to the building beyond fourth stories and multi-house occupancy. The purpose of this paper is to show the possibility to expect one hour fire resistance after reviewing the fire resistance performance caused from heat transfer analysis using FEM and that came from load-bearing fire tests, respectively. The surface temperatures from analysis with the models consisted of 140SL10 filled with mineral wool fully and partially and without mineral wool and two layer of fire resistance gypsum boards showed below the allowable temperature, 538℃ and the fire tests conducted using specimens made of the same structure used to analysis showed over 1 hour.
한국어
표면처리 경량형강 스터드와 방화석고보드 그리고 미네랄울로 구성된 내력벽체를 대상으로 1차원 열전달 해석으로 평가된 내화성능과 한국산업규격의 내화시험을 통하여 도출된 내화성능을 비교, 평가함으로써 향후 경량형강 이용 내력벽체의 해석적 내화성능 평가 가능성을 제시하고자 함을 연구목적으로 하여, 미네랄울에 의한 스터드 온도영향 그리고 내화성능 평가의 가능함을 확인하였다.
목차
1. 서론
2. 스틸하우스 내력벽체의 구성과 내화성능
3. 내력벽체의 내화성능 평가
3.1 해석적 내화성능 평가
3.2 시험적 내화성능 평가
4. 결론
참고문헌