Effect on Nutrient Heating of Fan Coil Unit System for Surplus Heat Recovery in Greenhouse
초록
영어
This study is nutrient heating effect to apply the surplus heat recovery in greenhouse using fan coil unit. Especially, this study was carried out to utilize a surplus heat in greenhouse. This fan coil unit system was composed of a water tank, a fan coil unit, a circulating pump and a water-water heat exchanger. As the result, Temperature difference duing to fan coil unit in greenhouse showed that air temperature at experimental greenhouse on fan , comparison greenhouse were 28.3℃, 33.9℃, respectively. heat ratio showed that exchanged energy quantity in fan coil unit was 19,900∼28,880kcal/h, respectively. It was found that difference of nutrient temperature due to surplus heat recovery, water tank temperature were 19.2∼21.5℃ and 16.2∼18.3℃, The temperature variation of nutrient temperature was about 3℃ and higher . Economic analysis of fan coil unit system was increased gross income cost by 804,787 won.